318 resultados para IEC 61850


Relevância:

100.00% 100.00%

Publicador:

Resumo:

This letter presents a technique to assess the overall network performance of sampled value process buses based on IEC 61850-9-2 using measurements from a single location in the network. The method is based upon the use of Ethernet cards with externally synchronized time stamping, and characteristics of the process bus protocol. The application and utility of the method is demonstrated by measuring latency introduced by Ethernet switches. Network latency can be measured from a single set of captures, rather than comparing source and destination captures. Absolute latency measures will greatly assist the design testing, commissioning and maintenance of these critical data networks.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

New substation automation applications, such as sampled value process buses and synchrophasors, require sampling accuracy of 1 µs or better. The Precision Time Protocol (PTP), IEEE Std 1588, achieves this level of performance and integrates well into Ethernet based substation networks. This paper takes a systematic approach to the performance evaluation of commercially available PTP devices (grandmaster, slave, transparent and boundary clocks) from a variety of manufacturers. The ``error budget'' is set by the performance requirements of each application. The ``expenditure'' of this error budget by each component is valuable information for a system designer. The component information is used to design a synchronization system that meets the overall functional requirements. The quantitative performance data presented shows that this testing is effective and informative. Results from testing PTP performance in the presence of sampled value process bus traffic demonstrate the benefit of a ``bottom up'' component testing approach combined with ``top down'' system verification tests. A test method that uses a precision Ethernet capture card, rather than dedicated PTP test sets, to determine the Correction Field Error of transparent clocks is presented. This test is particularly relevant for highly loaded Ethernet networks with stringent timing requirements. The methods presented can be used for development purposes by manufacturers, or by system integrators for acceptance testing. A sampled value process bus was used as the test application for the systematic approach described in this paper. The test approach was applied, components were selected, and the system performance verified to meet the application's requirements. Systematic testing, as presented in this paper, is applicable to a range of industries that use, rather than develop, PTP for time transfer.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Process bus networks are the next stage in the evolution of substation design, bringing digital technology to the high voltage switchyard. Benefits of process buses include facilitating the use of Non-Conventional Instrument Transformers, improved disturbance recording and phasor measurement and the removal of costly, and potentially hazardous, copper cabling from substation switchyards and control rooms. This paper examines the role a process bus plays in an IEC 61850 based Substation Automation System. Measurements taken from a process bus substation are used to develop an understanding of the network characteristics of "whole of substation" process buses. The concept of "coherent transmission" is presented and the impact of this on Ethernet switches is examined. Experiments based on substation observations are used to investigate in detail the behavior of Ethernet switches with sampled value traffic. Test methods that can be used to assess the adequacy of a network are proposed, and examples of the application and interpretation of these tests are provided. Once sampled value frames are queued by an Ethernet switch the additional delay incurred by subsequent switches is minimal, and this allows their use in switchyards to further reduce communications cabling, without significantly impacting operation. The performance and reliability of a process bus network operating with close to the theoretical maximum number of digital sampling units (merging units or electronic instrument transformers) was investigated with networking equipment from several vendors, and has been demonstrated to be acceptable.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

New substation technology, such as non-conventional instrument transformers,and a need to reduce design and construction costs, are driving the adoption of Ethernet based digital process bus networks for high voltage substations. Protection and control applications can share a process bus, making more efficient use of the network infrastructure. This paper classifies and defines performance requirements for the protocols used in a process bus on the basis of application. These include GOOSE, SNMP and IEC 61850-9-2 sampled values. A method, based on the Multiple Spanning Tree Protocol (MSTP) and virtual local area networks, is presented that separates management and monitoring traffic from the rest of the process bus. A quantitative investigation of the interaction between various protocols used in a process bus is described. These tests also validate the effectiveness of the MSTP based traffic segregation method. While this paper focusses on a substation automation network, the results are applicable to other real-time industrial networks that implement multiple protocols. High volume sampled value data and time-critical circuit breaker tripping commands do not interact on a full duplex switched Ethernet network, even under very high network load conditions. This enables an efficient digital network to replace a large number of conventional analog connections between control rooms and high voltage switchyards.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

The IEC 61850 family of standards for substation communication systems were released in the early 2000s, and include IEC 61850-8-1 and IEC 61850-9-2 that enable Ethernet to be used for process-level connections between transmission substation switchyards and control rooms. This paper presents an investigation of process bus protection performance, as the in-service behavior of multi-function process buses is largely unknown. An experimental approach was adopted that used a Real Time Digital Simulator and 'live' substation automation devices. The effect of sampling synchronization error and network traffic on transformer differential protection performance was assessed and compared to conventional hard-wired connections. Ethernet was used for all sampled value measurements, circuit breaker tripping, transformer tap-changer position reports and Precision Time Protocol synchronization of sampled value merging unit sampling. Test results showed that the protection relay under investigation operated correctly with process bus network traffic approaching 100% capacity. The protection system was not adversely affected by synchronizing errors significantly larger than the standards permit, suggesting these requirements may be overly conservative. This 'closed loop' approach, using substation automation hardware, validated the operation of protection relays under extreme conditions. Digital connections using a single shared Ethernet network outperformed conventional hard-wired solutions.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

This thesis has developed a new approach to trace virtual protection signals in Electrical substation networks. The main goal of the research was to analyse the contents of the virtual signals transferred, using third party software. In doing so, a comprehensive test was done on a distance protection relay, using non-conventional test equipment.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

While the implementation of the IEC 61850 standard has significantly enhanced the performance of communications in electrical substations, it has also increased the complexity of the system. Subsequently, these added elaborations have introduced new challenges in relation to the skills and tools required for the design, test and maintenance of 61850-compatible substations. This paper describes a practical experience of testing a protection relay using a non-conventional test equipment; in addition, it proposes a third party software technique to reveal the contents of the packets transferred on the substation network. Using this approach, the standard objects can be linked and interpreted to what the end-users normally see in the IED and test equipment proprietary software programs.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

The increased construction and reconstruction of smart substations has exposed a problem with version management of substation configuration description language (SCL) files due to frequent changes. This paper proposes a comparative approach for differentiation of smart substation SCL configuration files. A comparison model for SCL configuration files is built in this method, which is based on the SCL structure and abstract model defined by IEC 61850. The proposed approach adopts the algorithms of depth-first traversal, sorting, and cross comparison in order to rapidly identify differences of changed SCL configuration files. This approach can also be utilized to detect malicious tampering or illegal manipulation tailoring for SCL files. SCL comparison software is developed using the Qt platform to validate the feasibility and effectiveness of the proposed approach.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Cyber-attacks against Smart Grids have been found in the real world. Malware such as Havex and BlackEnergy have been found targeting industrial control systems (ICS) and researchers have shown that cyber-attacks can exploit vulnerabilities in widely used Smart Grid communication standards. This paper addresses a deep investigation of attacks against the manufacturing message specification of IEC 61850, which is expected to become one of the most widely used communication services in Smart Grids. We investigate how an attacker can build a custom tool to execute man-in-the-middle attacks, manipulate data, and affect the physical system. Attack capabilities are demonstrated based on NESCOR scenarios to make it possible to thoroughly test these scenarios in a real system. The goal is to help understand the potential for such attacks, and to aid the development and testing of cyber security solutions. An attack use-case is presented that focuses on the standard for power utility automation, IEC 61850 in the context of inverter-based distributed energy resource devices; especially photovoltaic (PV) generators.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

With the development and deployment of IEC 61850 based smart substations, cybersecurity vulnerabilities of supervisory control and data acquisition (SCADA) systems are increasingly emerging. In response to the emergence of cybersecurity vulnerabilities in smart substations, a test-bed is indispensable to enable cybersecurity experimentation. In this paper, a comprehensive and realistic cyber-physical test-bed has been built to investigate potential cybersecurity vulnerabilities and the impact of cyber-attacks on IEC 61850 based smart substations. This test-bed is close to a real production type environment, and has the ability to carry out end-to-end testing of cyber-attacks and physical consequences. A fuzz testing approach is proposed for detecting IEC 61850 based intelligent electronic devices (IEDs) and validated in the proposed test-bed.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

La evolución de las redes eléctricas se dirige hacia lo que se conoce como “Smart Grids” o “Redes Eléctricas Inteligentes”. Estas “Smart Grids” se componen de subestaciones eléctricas, que a su vez se componen de unos dispositivos llamados IEDs (Dispositivos Electrónicos Inteligentes – Intelligent Electronic Devices). El diseño de IEDs se encuentra definido en la norma IEC 61850, que especifica además un Lenguaje de Configuración de Subestaciones (Substation Configuration Language SCL) para la definición de la configuración de subestaciones y sus IEDs. Hoy en día, este estándar internacional no sólo se utiliza para diseñar correctamente IEDs y asegurar su interoperabilidad, sino que también se utiliza para el diseño de otros dispositivos de la red eléctrica, como por ejemplo, medidores inteligentes. Sin embargo, aunque existe una tendencia cada vez mayor del uso de este estándar, la comprensión y el manejo del mismo resulta difícil debido al gran volumen de información que lo compone y del nivel de detalle que utiliza, por lo que su uso para el diseño de IEDs se hace tedioso sin la ayuda de un soporte software. Es por ello que, para facilitar la aplicación del estándar IEC 61850 en el diseño de IEDs se han desarrollado herramientas como “Visual SCL”, “SCL Explorer” o “61850 SCLVisual Design Tool”. En concreto, “61850 SCLVisual Design Tool” es una herramienta gráfica para el modelado de subestaciones electricas, generada mediante el uso de los frameworks Eclipse Modeling Framework (EMF) y Epsilon Generative Modeling Technologies (GMT) y desarrollada por el grupo de investigación SYST de la UPM. El objetivo de este proyecto es añadir una nueva funcionalidad a la herramienta “61850 Visual SCL DesignTool”. Esta nueva funcionalidad consiste en la generación automática de un fichero de configuración de subestaciones eléctricas según el estándar IEC 61850 a partir de de una herramienta de diseño gráfico. Este fichero, se denomina SCD (Substation Configuration Description), y se trata de un fichero XML conforme a un esquema XSD (XML Schema Definition) mediante el que se define el lenguaje de configuración de subestaciones SCL del IEC 61850. Para el desarrollo de este proyecto, es necesario el estudio del lenguaje para la configuración de subestaciones SCL, así como del lenguaje gráfico específico de dominio definido por la herramienta “61850 SCLVisual Design Tool”, la estructura de los ficheros SCD, y finalmente, del lenguaje EGL (Epsilon Generation Language) para la transformación y generación automática de código a partir de modelos EMF. ABSTRACT Electrical networks are evolving to “Smart Grids”. Smart Grids are composed of electrical substations that in turn are composed of devices called IEDs (Intelligent Electronic Devices). The design of IEDs is defined by the IEC 61850 standard, which also specifies a Substation Configuration Languaje (SCL) used to define the configuration of substations and their IEDs. Nowadays, this international standard is not only used to design properly IEDs and guarantee their interoperability, but it is also used to design different electrical network devices, such as, smart meters. However, although the use of this standard is growing, its compression as well as its management, is still difficult due to its large volume of information and its level of detail. As a result, designing IEDs becomes a tedious task without a software support. As a consequence of this, in order to make easier the application of the IEC 61850 standard while designing IEDs, some software tools have been developed, such as: “Visual SCL”, “SCL Explorer” or “61850 SCLVisual Design Tool”. In particular, “61850 SCLVisual Design Tool” is a graphical tool used to make electrical substations models, and developed with the Eclipse Modeling Framework (EMF) and Epsilon Generative Modeling Technologies (GMT) by the research group SYST of the UPM. The aim of this project is to add a new functionality to “61850 Visual SCL DesignTool”. This new functionality consists of the automatic code generation of a substation configuration file according to the IEC 61850 standard. This file is called SCD (Substation Configuration Description), and it is a XML file that follows a XSD (XML Schema Definition) that defines the Substation Configuration Language (SCL) of the IEC 61850. In order to develop this project, it is necessary to study the Substation Configuration Language (SCL), the domain-specific graphical languaje defined by the tool “61850 SCLVisual Design Tool”, the structure of a SCD file, and the Epsilon Generation Language (EGL) used for the automatic code generation from EMF models

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Desde seu lançamento, em 2002, a Norma IEC 61850 vem evoluindo para se tornar o padrão adotado nos Sistemas de Automação de Subestações. Dentre seus vários aspectos, destacam- se os serviços de tempo real, que permitem a implementação de funções de automação e de proteção dentro da subestação através da troca de mensagens específicas entre Dispositivos Eletrônicos Inteligentes através de um barramento digital de rede de dados. O objetivo central deste trabalho é explorar algumas das questões que envolvem a implementação de uma classe de serviços de tempo real: a transmissão de valores amostrados através de Serviços SMV, definidos pela Norma IEC 61850-9. Primeiramente, apresenta-se um breve resumo das principais características da Norma IEC 61850 que possibilitam o atendimento dos três requisitos por ela estabelecidos como base: a interoperabilidade entre dispositivos de diferentes fabricantes, a versatilidade na configuração e reconfiguração do Sistema de Automação da Subestação, e a possibilidade de implementação de novas tecnologias. Em seguida, explora-se com maior profundidade todos os aspectos relevantes à implementação dos Serviços SMV. Devido à complexidade deste assunto, o autor propõe abordá-lo sob a ótica de cinco tópicos interdependentes: variações da Norma IEC 61850-9, confiabilidade do barramento de processo, sincronismo de tempo, análise da qualidade da medição e segurança cibernética. Com base nos resultados apresentados neste estudo, propõem-se duas plataformas, um protótipo de Transformador de Potencial Óptico e um protótipo de Relé de Proteção Diferencial para transformadores de potência, com o objetivo de explorar alguns dos aspectos pertinentes à implementação de um barramento de processo de acordo com a Norma IEC 61850-9. Também foram realizados testes de geração e transmissão de mensagens contendo valores de amostras de tensão/corrente do sistema elétrico (denominadas de SV Messages) com a finalidade de implementá-las de fato e avaliar as ferramentas de mercado disponíveis. Por fim foi proposto um modelo para a simulação do sistema de potência em conjunto com a rede de comunicação utilizando o programa Matlab/Simulink. O autor espera que este trabalho contribua para esclarecer os vários conceitos envolvidos na implementação do barramento de processo definido pela Norma IEC 61850-9, auxiliando na pesquisa e no desenvolvimento de novas ferramentas e dispositivos, e no aprimoramento da Norma IEC 61850.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Emerging cybersecurity vulnerabilities in supervisory control and data acquisition (SCADA) systems are becoming urgent engineering issues for modern substations. This paper proposes a novel intrusion detection system (IDS) tailored for cybersecurity of IEC 61850 based substations. The proposed IDS integrates physical knowledge, protocol specifications and logical behaviours to provide a comprehensive and effective solution that is able to mitigate various cyberattacks. The proposed approach comprises access control detection, protocol whitelisting, model-based detection, and multi-parameter based detection. This SCADA-specific IDS is implemented and validated using a comprehensive and realistic cyber-physical test-bed and data from a real 500kV smart substation.